Large Private Office - ASHRAE 90.1 (2010) Compliant

Space 250 SqFt
Dimming with DLM product

Large Private Office DLM Solution Reflected Ceiling Diagram

 

Bill Of Materials

Quantity

Part Number

Description

1

LMRC-102 2-Relay Room Controller

1

LMDW-102 2-Button Dual Tech Wall Switch Occupancy Sensor

1

WRC-TX-LM Plug Load RF Transmitter

4

WRC-20-1 Plug Load Half Controlled Receptacle

-

LMRJ Pre-Terminated Cable

Quantity

:

1

Part Number: LMRC-102

Description

:
2-Relay Room Controller

Quantity

:

1

Part Number: LMDW-102

Description

:
2-Button Dual Tech Wall Switch Occupancy Sensor

Quantity

:

1

Part Number: WRC-TX-LM

Description

:
Plug Load RF Transmitter

Quantity

:

4

Part Number: WRC-20-1

Description

:
Plug Load Half Controlled Receptacle

Quantity

:

-

Part Number: LMRJ

Description

:
Pre-Terminated Cable

Code Requirements

Code

Description

9.4.1

Manual On / Partial Auto On

9.4.1.1 Auto Shut Off
9.4.1.2 Space Control
9.4.1.2(a) Bi-level Control
8.4.2 Auto Receptacle Control

Code

:

9.4.1

Description

:

Manual On / Partial Auto On

Code

:
9.4.1.1

Description

:
Auto Shut Off

Code

:
9.4.1.2

Description

:
Space Control

Code

:
9.4.1.2(a)

Description

:
Bi-level Control

Code

:
8.4.2

Description

:
Auto Receptacle Control

Sequence of Operation

  1. Lighting (a) auto On to 50% and controlled receptacles auto On when occupancy detected.
  2. Space manual control On/Off and bi-level 50% control of lighting (a, b) with wall switch.
  3. Auto off all lighting and controlled receptacles within 30 minutes of occupants leaving.

Design Considerations

  1. When the primary sidelight area is 250ft2 or larger, it must have automatic daylight responsive controls installed for all general lighting in that area.
  2. Receptacle control can be designed using either an RF transmitter with receptacle RF receivers, or can be hardwired to receptacles using an LMPL-101 Plug Load Room Controller.
  3. Time scheduling, demand response and remote programming/diagnostic functions are enabled with installation of the LMBC-300 Network Bridge for system connectivity.
  4. To integrate occupancy detection control with the HVAC System, use a LMRL-100 Isolated Relay Interface.