Large Private Office - ASHRAE 90.1 (2013) Compliant

Space 250 SqFt
Dimming with DLM product

ASHRAE Large Private Office

 

Bill Of Materials

Quantity

Part Number

Description

1 LMRC-111 1-Relay Room Controller, 0-10V Dimming
1 LMDX-100 Corner Mount Dual Tech Occupancy Sensor
1 LMDM-101 1-Button Dimming Wall Switch
1 LMLS-400 Photosensor, Closed Loop

1

LMPL-101 Plug Load Room Controller

-

LMRJ

Pre-Terminated Cable

Quantity

:
1
Part Number: LMRC-111

Description

:
1-Relay Room Controller, 0-10V Dimming

Quantity

:
1
Part Number: LMDX-100

Description

:
Corner Mount Dual Tech Occupancy Sensor

Quantity

:
1
Part Number: LMDM-101

Description

:
1-Button Dimming Wall Switch

Quantity

:
1
Part Number: LMLS-400

Description

:
Photosensor, Closed Loop

Quantity

:

1

Part Number: LMPL-101

Description

:
Plug Load Room Controller

Quantity

:

-

Part Number: LMRJ

Description

:

Pre-Terminated Cable

Code Requirements

Code

Description

9.4.1.1(a)

Local Control Device

9.4.1.1(b, c) Manual On / Partial Auto On
9.4.1.1(d) Bi-level Control
9.4.1.1(e) Auto Daylight Responsive
9.4.1.1(h) Auto Full Off
8.4.2 Auto Receptacle Control

Code

:

9.4.1.1(a)

Description

:

Local Control Device

Code

:
9.4.1.1(b, c)

Description

:
Manual On / Partial Auto On

Code

:
9.4.1.1(d)

Description

:
Bi-level Control

Code

:
9.4.1.1(e)

Description

:
Auto Daylight Responsive

Code

:
9.4.1.1(h)

Description

:
Auto Full Off

Code

:
8.4.2

Description

:
Auto Receptacle Control

Sequence of Operation

  1. Lighting auto On to 50% and controlled receptacles auto On when occupancy detected.
  2. Manual On/Off/Dim lighting with dimmer switch.
  3. Lighting in primary daylight zone will continuously dim based on daylight contribution to maintain at least 35FC at task level.
  4. Auto off all lighting and controlled receptacles within 20 minutes of occupants leaving.

Design Considerations

  1. Receptacle control can be designed using either an RF transmitter with receptacle RF receivers, or can be hardwired to receptacles using an LMPL-101 Plug Load Room Controller.
  2. Time scheduling, demand response and remote programming/diagnostic functions are enabled with installation of the LMBC-300 Network Bridge for system connectivity.
  3. To integrate occupancy detection control with the HVAC System, use a LMRL-100 Isolated Relay Interface.