Wattstopper Wireless DLM Now Available!

Intelligent. Secure. Scalable.

Watch the Video

Menu
Search
Menu

Small Conference Room - CA Title 24 (2016) Compliant

Space >100Ft2, Bldg >10,000Ft2
Dimming with DLM product

TITLE24 Small Conference Room

 

Bill Of Materials

Quantity

Part Number

Description

1 LMRC-213 3-Relay Room Controller, 0-10V Dimming
1 LMDC-100 Ceiling Mount Dual Tech Occupancy Sensor
1 LMSW-105 5-Button Scene Switch

1

WRC-TX-LM Plug Load RF Transmitter

4

WRC-20-1 Plug Load Half Controlled Receptacle

1

LMBC-300 Wired Network Bridge

-

LMRJ Pre-Terminated Cable

Quantity

:
1
Part Number: LMRC-213

Description

:
3-Relay Room Controller, 0-10V Dimming

Quantity

:
1
Part Number: LMDC-100

Description

:
Ceiling Mount Dual Tech Occupancy Sensor

Quantity

:
1
Part Number: LMSW-105

Description

:
5-Button Scene Switch

Quantity

:

1

Part Number: WRC-TX-LM

Description

:
Plug Load RF Transmitter

Quantity

:

4

Part Number: WRC-20-1

Description

:
Plug Load Half Controlled Receptacle

Quantity

:

1

Part Number: LMBC-300

Description

:
Wired Network Bridge

Quantity

:

-

Part Number: LMRJ

Description

:
Pre-Terminated Cable

Code Requirements

Code

Description

130.1(a)1-3 Area Controls
130.1(b) Multi-Level Controls
130.1(c)5 Occupancy Sensor Shut-Off Controls
130.1(e) Demand Responsive Controls
130.5(d) Receptacle Control

Code

:
130.1(a)1-3

Description

:
Area Controls

Code

:
130.1(b)

Description

:
Multi-Level Controls

Code

:
130.1(c)5

Description

:
Occupancy Sensor Shut-Off Controls

Code

:
130.1(e)

Description

:
Demand Responsive Controls

Code

:
130.5(d)

Description

:
Receptacle Control

Sequence of Operation

  1. General lighting (a) auto On to 50% and controlled receptacles auto On when occupancy detected.
  2. Manual On/Off/Dim of general lighting (a) and down lighting (b, c) with scene switch.
  3. Scene settings
    • General Lighting       (a) 100%, (b) 0%, (c) 0%
    • Presentation              (a) 75%, (b) 50%, (c) 100%
    • Video                            (a) 20%, (b) 75%, (c) 0%
    • All Off                           (a) 0%, (b) 0%, (c) 0%
  4. Auto off all lighting and controlled receptacles within 20 minutes of occupants leaving.
  5. A network demand response signal will reduce lighting level by a minimum of 15% of total lighting power.

Design Considerations

  1. Receptacle control can be designed using either an RF transmitter with receptacle RF receivers, or can be hardwired to receptacles using an LMPL-101 Plug Load Room Controller.
  2. Demand Response, time scheduling and remote programming functions are enabled by the LMBC-300 Network Bridge connectivity. If Demand Responsive 15% lighting power reduction (Title 24 130.1(e)) for this space is offset by more aggressive light reduction in other spaces, connection to the lighting control network may not be necessary, thereby not requiring the LMBC-300 Network Bridge and associated network wiring.
  3. To integrate occupancy detection control with the HVAC System, use a LMRL-100 Isolated Relay Interface.