Discontinued - Dual Tech Occupancy Sensor, 24VDC, Corner Mt, 40 Khz, USA
DT-200-U
Wattstopper
Bazaarvoice SAP Hybris Integration Version 2.8.1
The Wattstopper DT-200 Dual Technology occupancy sensors combine advanced passive infrared (PIR) and ultrasonic technologies into one unit. The combination of these technologies helps to eliminate false triggering problems even in difficult applications. The DT-200 turns lighting systems ON and OFF based on occupancy and ambient light levels. The DT-200 offers numerous operating modes that can be combined to create the ideal custom control. The sensors can be configured to turn lighting ON, and hold it ON as long as either or both technologies detect occupancy. After no movement is detected for the duration of the time delay (30 seconds to 30 minutes) the lights are switched OFF. A “walk-through” mode can turn lights OFF after only
3 minutes, if no activity is detected after 30 seconds of an occupancy detection. The DT-200 operates on 24VDC supplied by Wattstopper Power Packs. DT-200 sensors also have an isolated relay with Normally Open and Normally Closed contacts for interfacing with HVAC or EMS.
3 minutes, if no activity is detected after 30 seconds of an occupancy detection. The DT-200 operates on 24VDC supplied by Wattstopper Power Packs. DT-200 sensors also have an isolated relay with Normally Open and Normally Closed contacts for interfacing with HVAC or EMS.
- Send
- Save as PDF
-
Added to Favorites Go to favoritesRemove from favorites?Something went wrong. Please try again later.
Features
- Advanced control logic based on RISC micro-controller provides: – Detection Signature Processing to eliminate false triggers and provides immunity to RFI and EMI – Walk-through Mode turns lights off three minutes after the area is initially occupied – ideal for brief visits, such as mail delivery – Available with built-in light level sensor featuring simple, one-step setup
- Sensors work with low-voltage momentary switches to provide manual control
- LEDs indicate occupancy detection
- Eight occupancy logic options provide the ability to customize control to meet application needs
- Available with isolated relay for integration with BAS or HVAC
- Swivel mounting bracket for convenient corner mounting to wall or ceiling
- BAA/TAA-compliant models available
Specifications
General Info
Color | White | ||
Product Series | DT-200 | ||
Type | Sensor | ||
Finish | Glossy | ||
Application Sector | Commercial | ||
Product Line | Wattstopper | ||
Country Of Origin | United States | ||
Features | Adjustable Time Delay, Indicator Lights, Isolated Relay, Light Level Sensor, Power Pack Required, Sensitivity Adjustment, Test Mode, Walkthrough Mode | ||
Included | J-Box Cover Plate, Sensor Mask, Swivel Bracket | ||
Installation Location | Ceiling, Wall | ||
Switch Type | Motion Sensor | ||
Warranty Type | 5-Year | ||
Standard | UL, cUL | ||
UPC Number | 754182910748 |
Dimensions
Product Depth US | 3.1 in | ||
Product Height US | 4.3 in | ||
Product Volume US | 66.1 cu in | ||
Product Width US | 3.4 in | ||
Product Weight US | 0.3 lb |
Technical Information
Current Draw | 33 mA | ||
On Function | Auto On | ||
Wire Connection Type | Flying Leads | ||
Compatibility | BZ Power Packs, Wattstopper PLUS Sensor Interface Module | ||
Has Battery | No | ||
Indicator | PIR Detection LED, Ultrasonic Detection LED | ||
Indoor/Outdoor | Indoor | ||
Input Voltage | 18 to 28 VDC/VAC | ||
Load Rating | 1 A @ 30 VDC | ||
Mounting Type | J-Box, Surface, Swivel Bracket | ||
Number of Buttons | 0 | ||
Timer Type | DIP Switch | ||
Timer Duration | 30 Seconds, 5-30 Minutes | ||
Operating Temperature | 0°-55°C, 32°-131°F | ||
Operating Temperature Max | 131 °F | ||
Operating Temperature Min | 32 °F | ||
Operating Humidity | 5-95% RH (Non-Condensing) | ||
Sensing Range | 38 ft, 55 ft | ||
Sensor Type | Occupancy | ||
Sensor Technology | Passive Infrared (PIR), Ultrasonic | ||
Sensor Coverage | 2000 sq ft | ||
Sensor Coverage Pattern | 90 deg | ||
Sensor Mounting Height | 10 ft | ||
Ultrasonic Frequency | 40 kHz | ||
Storage Temperature | 23° - 176° F, -5° - 80° C | ||
Engraving Type | Blank |
Resources
Instruction Sheet
CAD Drawings
57-003-1 - Any 8-Wire Occupancy Sensor "Standard Schematic"
dxf
57-003-1 - Any 8-Wire Occupancy Sensor "Standard Schematic"
pdf
57-003-1 - Any 8-Wire Occupancy Sensor "Standard Schematic"
png
57-003-1 - Any 8-Wire Occupancy Sensor "Standard Schematic"
pdf
57-003-1 - Any 8-Wire Occupancy Sensor "Standard Schematic"
dwg
57-010 - Multiple Occupancy Sensors Using One Power Pack
dxf
57-010 - Multiple Occupancy Sensors Using One Power Pack
png
57-010 - Multiple Occupancy Sensors Using One Power Pack
dwg
57-010 - Multiple Occupancy Sensors Using One Power Pack
pdf
57-039-5 - DT-200/CX Series Mounting Detail with Pendant Mounted Fixtures
pdf
57-039-5 - DT-200/CX Series Mounting Detail with Pendant Mounted Fixtures
dxf
57-039-5 - DT-200/CX Series Mounting Detail with Pendant Mounted Fixtures
png
57-039-5 - DT-200/CX Series Mounting Detail with Pendant Mounted Fixtures
dwg
57-039-6 - DT & CX Series Sensor Installation
png
57-039-6 - DT & CX Series Sensor Installation
pdf
57-039-6 - DT & CX Series Sensor Installation
dxf
57-039-6 - DT & CX Series Sensor Installation
dwg
57-041-1 - 8-Wire Sensor Interfacing With A Thermostat
dxf
57-041-1 - 8-Wire Sensor Interfacing With A Thermostat
dwg
57-041-1 - 8-Wire Sensor Interfacing With A Thermostat
pdf
57-041-1 - 8-Wire Sensor Interfacing With A Thermostat
png
60-601-2 - LI/LP Relay Panels Occupancy Sensor Connection
pdf
60-601-2 - LI/LP Relay Panels Occupancy Sensor Connection
dxf
60-601-2 - LI/LP Relay Panels Occupancy Sensor Connection
png
60-601-2 - LI/LP Relay Panels Occupancy Sensor Connection
dwg
DT-200
png
DT-200
dwg
DT-200
dxf
DT-200cp - DT-200 Coverage Pattern
dxf
DT-200cp - DT-200 Coverage Pattern
png
DT-200cp - DT-200 Coverage Pattern
dwg
View More
Specifications
Case Studies
Lighting Controls from The Watt Stopper Contribute to "Greenest" Building
pdf
The Watt Stopper Occupancy Sensors Reduce University Lighting Load by 30%
pdf
The Watt Stoppers Dual Technology Occupancy Sensors Save $11,500/year at Des Moines Area Community College
pdf
Watt Stopper/Legrand helps NRG Systems realize big savings
pdf
View More
Reviews
Bazaarvoice SAP Hybris Integration Version 2.8.1
Questions & Answers
What type of box does this occupancy sensor mount to? The instruction sheet says a 3.0" mudring with a 4" octagonal box. I'm not familiar with a mudring that is compatible with an octagon box. I'm assuming it means a 3" round mudring, is that correct?
Yes, it mounts to a 3" mudring.