Discontinued - Dual Tech Wall Switch Occupancy Sensor, 347V, Ivory
DSW-301-347-I
Wattstopper
Dual Tech Wall Switch Occupancy Sensor is rated
out of
5 by
1.
Bazaarvoice SAP Hybris Integration Version 2.8.1
Replaced by DSW-301-347-W
The DSW-301 dual technology wall switch sensor turns lights OFF and ON based on occupancy. It combines the benefits of passive infrared (PIR) and ultrasonic detection technologies. The DSW-301 replaces existing wall switches and fits behind a standard decorator wall plate.
- Send
- Save as PDF
-
Added to Favorites Go to favoritesRemove from favorites?Something went wrong. Please try again later.
Features
- Collection consolidated of in 347 V to white option
- Zero-crossing for long relay life
- Vandal resistant lens combines precise coverage with durability
- Selectable walk-through mode turns lights off three minutes after initial occupancy if no motion is detected after the first 30 seconds
- Test mode allows quick and easy adjustments
- Selectable audible alert for impending shutoff
- In automatic mode, sensor returns automatically to Auto-ON after lights are turned off manually; ideal for presentations
- Four occupancy logic options to customize control to meet application needs
- The DSW-301 sensors can be wired together for convenient control of a common load only with other DSW-301 sensors
Specifications
General Info
Product Line | Wattstopper | ||
Replaced by Part Number | DSW-301-347-W | ||
Color | Ivory | ||
UPC Number | 754182935659 | ||
Country Of Origin | China |
Dimensions
Product Width US | 3.8 in | ||
Product Weight US | 2.3 lb | ||
Product Volume US | 37.1 cu in | ||
Product Depth US | 3.8 in | ||
Product Height US | 6.5 in |
Additional Information
RoHS Compliant | Yes | This product meets the material restrictions of Article 4 of the RoHS Directive (2011/65/EU), including Commission Delegated Directive 2015/863. | |
Security | Yes | This product is ioXt certified |
Technical Information
Sensor Type | Occupancy | ||
Amperage | 4.3 A | ||
Sensor Technology | Passive Infrared (PIR), Ultrasonic | ||
Wattage | 1500 W |
Reviews
Rated 1 out of
5
by
renemcclugard from
horrible for office setting
This is horrible for an office setting if you work at a computer or are required to read/write for extended periods. The lights constantly turn off, requiring you to get up to turn the lights back on.
Date published: 2024-09-08
Bazaarvoice SAP Hybris Integration Version 2.8.1
Questions & Answers
Can this be use on one side of a 3 way system with the other switch a regular 3 way>
Hello Cody,
The DSW301 Occupancy sensor supports Multi-way functionality for use with additional DSW301 sensors. The DSW301 will not work with a traditional 3-way switch and must be paired with another DSW301 for 3-way applications.
Best Regards,
Technical Support
Date published: 2023-06-16
Can I control bathroom exhaust fan with this switch?
Hello,
Occupancy Dual Technology Sensors DSW301 will support the following loads:
120VAC; 50/60Hz or 277VAC; 50/60Hz
120VAC: 0-1000W ballast, LED, tungsten, 1/6 hp
277VAC: 0-1200W ballast, LED, 1/6 hp
Best Regards,
Technical Support
Date published: 2023-05-26
Will a DSW301W work without a ground connection?
Hello,
DSW301W - The ground wire (green) must be fastened to ground for the sensor to work properly.
Best Regards,
Technical Support
Date published: 2024-04-17
Is the watt stopper dsw 301w also a 3-way switch
Hello,
DSW-301-W supports the following Multi-way features: (Total of 4 Sensors)
The Multi-Way capability is available on all models. Sensors can easily be wired together for convenient control of a common load. When wiring this way, only use 300 series sensors. Multi-Way in 300 series is not compatible with prior sensor models.
The following principles apply for Multi-Way:
• All units should be on the same phase.
• All units can see each other’s push-button events and respond accordingly.
• All units can see each other’s PIR trigger event. The response will be determined by the Light Level setting and/or conditions of the space of the detecting sensor.
• The time delay for all units is defined by the unit with the smallest time delay
Best Regards,
Technical Support
Date published: 2023-03-06
Is there any way to purchase a replacement plastic lens for this? During construction, mine popped off and was swept up and disappeared, and it seems like such a cheap little piece that should be replaceable as it is easy to remove and/or damage.
The lens is not available as an individual part. Please contact Wattstopper Technical Support for further information. 800-879-8585.
Date published: 2022-12-21
What relay positions are needed to return this until back to basic on/off (no motion sensing) functionality?
Reset to Default
Use the DIP Switch Settings tables shown below to return features to factory settings.
To reset the DSW, press and hold the Relay 1 button for 10 seconds until a triple beep sounds. This resets the sensor and disables light level control (the brightest ambient light will not hold the light OFF).
Date published: 2023-11-18
Bazaarvoice SAP Hybris Integration Version 2.8.1