DLM N4 JACE 8000, Max 125 Rooms
LMJA-8125
Wattstopper
Bazaarvoice SAP Hybris Integration Version 2.8.1
The LMJA-8xxx is a network controller designed to communicate with wired and wireless DLM network Bridges, for local in-room wired networks and/or LMCP panels. It provides control, monitoring, adjustment, and standard or Human Centric Lighting (HCL) scheduling functionality for networked DLM systems. The Network Supervisor is a PC server running similar software designed to coordinate control of multiple LMJA-8xxx’s and store historical data.
- Send
- Save as PDF
-
Added to Favorites Go to favoritesRemove from favorites?Something went wrong. Please try again later.
Features
- Communicates all DLM local network data and device information via the segment network dataline
- Browser-based UI uses SSL industry standard communications and can be accessed via direct TCP/IP connection, local LAN or via the Internet
- Integration with BAS standard BACnet objects to represent DLM Through Segman 2.4 only
- Allows remote changes to occupancy sensor and daylighting sensor settings in real time
- Adjusts scheduling of normal and after hours
- Create standard & HCL lighting schedules.
- Schedules may be repeating seven day, calendar event based or astronomic control
- Allows real time current monitoring of rooms and groups when using load controllers with current monitoring circuitry (e.g. LMRC-2xx or LMPL-201)
Specifications
General Info
Color | Gray | ||
Product Series | LMJA | ||
Type | Network Controller | ||
Finish | Matte | ||
Application Sector | Commercial | ||
Product Line | Wattstopper | ||
Country Of Origin | United States | ||
Features | 125 Max Rooms | ||
Included | Micro SD Card, NP-PS1 Power Supply | ||
Installation Location | Panel | ||
Warranty Type | 1-Year | ||
UPC Number | 754182944378 |
Dimensions
Product Depth US | 2.4 in | ||
Product Height US | 4.4 in | ||
Product Volume US | 73.92 cu in | ||
Product Width US | 7.0 in | ||
Product Weight US | 0.9 lb |
Technical Information
Max Distance Support | 4000 ft | ||
Number of Connections | 5 | ||
Topology | Daisy Chain | ||
Compatibility | DLM Wired | ||
Indicator | LED Light | ||
Indoor/Outdoor | Indoor | ||
Input Voltage | 24 VDC/VAC | ||
Device Interface | RS-485 | ||
Mounting Type | DIN Rail | ||
Network | LAN - Ethernet | ||
Number of Ports | 2 | ||
Operating System | Niagara | ||
Operating Temperature | -20°-60°C | ||
Operating Temperature Max | 60 °C | ||
Operating Temperature Min | -20 °C | ||
Operating Humidity | 5-95% RH (Non-Condensing) | ||
Protocol | MS/TP | ||
Security Method | User Authentication | ||
Software Requirements | Workbench | ||
Storage Temperature | -40° - 185° F |