Breakroom|Kitchen - ASHRAE 90.1 (2013) Compliant

On/Off Switching with DLM Product

ASHRAE Breakroom

 

Bill Of Materials

Quantity

Part Number

Description

1

LMRC-101 1-Relay Room Controller

1

LMRC-102 2-Relay Room Controller

1

LMDW-102 2-Button Dual Tech Wall Switch Occupancy Sensor

1

LMSW-101 1-Button Digital Wall Switch

1

LMPL-101 Plug Load Room Controller
- LMRJ

Pre-Terminated Cable

Quantity

:

1

Part Number: LMRC-101

Description

:
1-Relay Room Controller

Quantity

:

1

Part Number: LMRC-102

Description

:
2-Relay Room Controller

Quantity

:

1

Part Number: LMDW-102

Description

:
2-Button Dual Tech Wall Switch Occupancy Sensor

Quantity

:

1

Part Number: LMSW-101

Description

:
1-Button Digital Wall Switch

Quantity

:

1

Part Number: LMPL-101

Description

:
Plug Load Room Controller

Quantity

:
-
Part Number: LMRJ

Description

:

Pre-Terminated Cable

Code Requirements

Code

Description

9.4.1.1(a)

Local Control Device

9.4.1.1(b, c) Manual On / Partial Auto On
9.4.1.1(d) Bi-level Control
9.4.1.1(h) Auto Full Off
8.4.2 Auto Receptacle Control

Code

:

9.4.1.1(a)

Description

:

Local Control Device

Code

:
9.4.1.1(b, c)

Description

:
Manual On / Partial Auto On

Code

:
9.4.1.1(d)

Description

:
Bi-level Control

Code

:
9.4.1.1(h)

Description

:
Auto Full Off

Code

:
8.4.2

Description

:
Auto Receptacle Control

Sequence of Operation

  1. Lighting (a) auto On to 50% and controlled receptacles auto On when occupancy detected.
  2. Manual On/Off and bi-level 50% control of general lighting (a, b) with wall switch occupancy sensor.
  3. Manual On/Off control under cabinet lighting (c) with switch.
  4. Auto off all lighting and controlled receptacles within 20 minutes of occupants leaving.

Design Considerations

  1. Receptacle control can be designed using either an RF transmitter with receptacle RF receivers, or can be hardwired to receptacles using an LMPL-101 Plug Load Room Controller.
  2. A ceiling or corner mount occupancy sensor can be used instead of the wall switch occupancy sensor for larger rooms or to achieve a more specific area of occupancy detection coverage.
  3. Time scheduling, demand response and remote programming/diagnostic functions are enabled with installation of the LMBC-300 Network Bridge for system connectivity.
  4. To integrate occupancy detection control with the HVAC System, use a LMRL-101 Isolated Relay Interface.