Straight Blade Receptacle 50A 125/250V 3-Pole 4-Wire
- Send
- Save as PDF
-
FavoriteAdded to Favorites Go to favoritesRemove from favorites?Something went wrong. Please try again later.
Specifications
General Info
Product Line | Pass & Seymour | ||
UPC Number | 785007807905 | ||
Country Of Origin | China |
Listing Agencies / 3rd Party Agencies
CSA Listed | Yes | ||
cULus Listed | Yes |
Resources
Cutsheet
Reviews
Bazaarvoice SAP Hybris Integration Version 2.8.1
Questions & Answers
Is this rated for use with EV chargers?
The 3894 is rated for 50 amp circuits which allow up to 80% (40 amps) continuous load and 100 % load (50 amps) for up to 4 hours.
Devices are tested for heating at 100% rated load (50 amps) after undergoing 100 cycles of inserting and with drawing a plug making and breaking a 150% load (75amps), and 250 cycles prior to dielectric voltage break down test.
An EV charger is highly unlikely to draw full rated current when first plugged in so you will never see the degradation of the receptacle and plug blades we see during testing, so the receptacle should function at lower temperatures than allowed by UL under normal use.
Date published: 2022-09-22
What is the box fill for the 3894
Per NEC 314.16(B)(4) For each yoke or strap containing one or more devices or equipment, a double volume allowance in accordance with Table 314.16(B) shall be made for each yoke or strap based on the largest conductor connected to the device(s) or equipment supported by that yoke or strap.
Lets assume you are using 6AWG wire (good for 55 amps at 60C) the table requires 5 cubic inches for each 6 AWG conductor.
Since a device requires a double allowance in this scenario the device would require a deduction of 10 cubic inches.
The rest of the deductions would be determined by how the device is wired. The number of conductors, clamps, grounding conductors used in the installation would need to be known.
Please note that the size of the deduction for the device is based on the wire size. So, if you are using a higher rated wire (75C or 90C) for the installation the overall size of the deduction for the device would decrease.
Date published: 2022-07-19
What is the operating temperature range of this outlet? As is, what is the maximum temperature and minimum temperature that this outlet will still perform? (ex., installed in a garage, this outlet will need to function in both winter and summer weather)
Environmental Ratings:
Operating Temperature: Maximum continuous +75°C, minimum -40°C without impact
Date published: 2022-07-16
what is the operating temperature rage of this outlet?
The 3894 receptacle is rated for use with 75°C wire.
Date published: 2022-07-16
Is there any similar product but 208 V?
Our 3870 Power Outlet is 60A, 120/208V rated:
https://www.legrand.us/passandseymour/range-dryer/flush-mount/60a/3870.aspx
Date published: 2020-05-04
Can this be adapted to a standard 4 prong dryer outlet?
The 3894 is already a 4 wire dryer outlet so I would contact Technical Support so we can understand your inquiry better.
Pass & Seymour products
1.800.223-4185 opt 1
Mon - Fri: 8am - 8pm EST
(excluding holidays)
Email Us - tech.support@legrand.us
Date published: 2020-02-25
Are the terminals on this device rated for use with aluminum wire?
The 50A Power Oulet is rated for #10 – #6 AWG Copper/Copper-clad/Aluminum wire.
Date published: 2019-12-09
What is the rating of the 3894 receptacle to ground?
The 3894 Power Outlet is a 50A 125/250V rated receptacle.
Date published: 2022-07-16