DLM Triple Relay Room Controller, 0-10V, 347V
Bazaarvoice SAP Hybris Integration Version 2.8.1
LMRC-210 Series Digital Room Controllers include one, two or three relay(s) to switch a total of 15 or 20 amps, a highefficiency switching power supply and one 0-10 volt output per relay for control of dimmable loads including electronic ballasts (Advance Mark 7, or equivalent). They are the foundation of a Wattstopper Digital Lighting Management (DLM) system, and allow integration of occupancy sensors, daylighting controls and switches for energy-efficient lighting control.
- Send
- Save as PDF
-
Added to Favorites Go to favoritesRemove from favorites?Something went wrong. Please try again later.
Features
- Plenum-rated controllers with line voltage relay(s) and 0-10 volt dimming output(s)
- 120/230/240/277 volt and 347 volt models
- Plug to other components using Cat 5e cables with RJ45 connectors eliminating wiring errors
- Plug n’ Go automatic configuration for maximum energy efficiency
- Store load preset level and 16 scene preset levels for each load
- Support energy saving manual-on, bi-level, tri-level and dimming control strategies
Specifications
Color | White | ||
Product Series | LMRC | ||
Type | Room Controller | ||
Application Sector | Commercial | ||
Product Line | Wattstopper | ||
Country Of Origin | China | ||
Installation Location | Ceiling | ||
Warranty Type | 5-Year | ||
Standard | UL 924, UL 60730, UL 2043, cUL, FCC part 15, PEP, RoHS 2011/65/EC, ISO 14025:2010, ISO 14001, ISO 14040:2006, ISO 14044:2006 | ||
UPC Number | 754182928958 |
Product Depth US | 3.3 in | ||
Product Height US | 6.5 in | ||
Product Volume US | 226.0 cu in | ||
Product Width US | 6.5 in | ||
Product Weight US | 1.6 lb |
RoHS Compliant | Yes | This product meets the material restrictions of Article 4 of the RoHS Directive (2011/65/EU), including Commission Delegated Directive 2015/863. |
Current Draw | 15 A | ||
Number of Connections | 7 | ||
Topology | Free Topology | ||
Connector Type | RJ45, Terminal Block | ||
Dimming Compatibility | 0-10 V | ||
Indoor/Outdoor | Indoor | ||
Input Voltage | 347 VAC | ||
Line Frequency | 50 Hz, 60 Hz | ||
Mounting Type | 4 in Deep J-Box | ||
Number of Relays | 3 | ||
Operating Temperature | 0°-60°C, 32°-140°F | ||
Operating Temperature Max | 140 °F | ||
Operating Temperature Min | 32 °F | ||
Operating Humidity | 5-95% RH (Non-Condensing) | ||
Output Voltage | 24 VDC |
Resources
Cutsheet
Installation Instructions
CAD Drawings
BIM Models
Supporting Document
Customer CAD PDF
Software Downloads
White Papers & Tech Bulletins
Reviews
Bazaarvoice SAP Hybris Integration Version 2.8.1
Questions & Answers
Can you use a 3 way splitter (t tap) to connect 2 relay packs together with a device like a switch or a occ sensor.
my LMRC-212 relay turns on some loads but not all of them,what is wrong
How many occupancy sensors can I run off of this?
I have 8 LMDM-101 and 1 only LMSW-105 connected to a LMRC-213, the owners are complaining of operation lag of the switches. Both the LMDM and LMSW will turn the fixtures on but dimming and to turn off are intermittent. Any trouble shooting ideas?
My Load light is blinking and it’s turning the lights on and off what’s the problem because everything was working fine
When power is to my 213 the loads flash on and off
I would like to know if a LMRC-313 wattstopper is still a good part number or if it has been replaced with a new number.
Can the controller be programmed to automatically turn on all zones to 50%?
I have a LMRC-212 controller with the LMW-102 and LMDM-101 switches when dimming one load "lights" it dims the second set at the same time. Custome wants a second dimmer to dim one load at the time.
Can you program these to be auto on auto off?
Why is my LMRC 211 configuration light solid red When I click load A, it turns solid red and my devices on the network won't work(sensors, switches)
how to set up a lmrc-212 with 2 lmdm-101 in 3 way but each switch dims a separate zone
config. light not blinking on the controller. and wall switch unable to turn light on.
What dimmer would be recommended for use with led fixtures for this controller?
Can you Daisy 2 relay boxes together ?
what is the catalog number for LMRC-211 dimmer switch?
what is the strap with the brass clip used for?
Can the LMRC's incorporate a time clock?
Bazaarvoice SAP Hybris Integration Version 2.8.1