Conference Room - ASHRAE 90.1 (2010) Compliant

Space <5000Ft
Dimming with DLM product

Conference Room DLM Solution Reflected Ceiling Diagram

 

 

Bill Of Materials

Quantity

Part Number

Description

1 LMRC-213 3-Relay Room Controller, 0-10V Dimming
1 LMRC-112 2-Relay Room Controller, 0-10V Dimming
2 LMDC-100 Ceiling Mount Dual Tech Occupancy Sensor
2 LMSW-105 5-Button Scene Switch
1 LMLS-400 Photosensor, Closed Loop

1

LMDI-100 Serial Data (A/V) Interface

-

LMRJ

Pre-Terminated Cable

Quantity

:
1
Part Number: LMRC-213

Description

:
3-Relay Room Controller, 0-10V Dimming

Quantity

:
1
Part Number: LMRC-112

Description

:
2-Relay Room Controller, 0-10V Dimming

Quantity

:
2
Part Number: LMDC-100

Description

:
Ceiling Mount Dual Tech Occupancy Sensor

Quantity

:
2
Part Number: LMSW-105

Description

:
5-Button Scene Switch

Quantity

:
1
Part Number: LMLS-400

Description

:
Photosensor, Closed Loop

Quantity

:

1

Part Number: LMDI-100

Description

:
Serial Data (A/V) Interface

Quantity

:

-

Part Number: LMRJ

Description

:

Pre-Terminated Cable

Code Requirements

Code

Description

9.4.1

Manual On / Partial Auto On

9.4.1.1 Auto Shut Off
9.4.1.2 Space Control
9.4.1.2(a) Bi-Level Control
9.4.1.4 Auto Daylighting Control
9.4.1.6 Additional Control

Code

:

9.4.1

Description

:

Manual On / Partial Auto On

Code

:
9.4.1.1

Description

:
Auto Shut Off

Code

:
9.4.1.2

Description

:
Space Control

Code

:
9.4.1.2(a)

Description

:
Bi-Level Control

Code

:
9.4.1.4

Description

:
Auto Daylighting Control

Code

:
9.4.1.6

Description

:
Additional Control

Sequence of Operation

  1. General lighting (a, adz1) auto On to 50% when occupancy detected.
  2. Space manual On/Off/Dim general lighting (a, adz1) and down lighting (b, c, d) with scene switches.
  3. Scene settings
    1. General Lighting(a, adz1) 100%, (b) 0%, (c) 0%, (d) 0%
    2. Projection(a, adz1) 0%, (b) 75%, (c) 50%, (d) 0%
    3. Conferencing(a, adz1) 50%, (b) 50%, (c) 25%, (d) 50%
    4. All Off(a, adz1) 0%, (b) 0%, (c) 0%, (d) 0%
  4. Lighting in primary (adz1) daylight zones will continuously dim based on daylight contribution to maintain at least 35FC at task level.
  5. Auto off all lighting and A/V systems within 30 minutes of occupants leaving.

Design Considerations

  1. When the primary sidelight area is 250ft2 or larger, it must have automatic daylight responsive controls installed for all general lighting in that area.
  2. Although not required for this space type, receptacle control can be added for additional energy savings using either an RF transmitter with receptacle RF receivers, or hardwired receptacles with an LMPL-101 Plug Load Room Controller.
  3. Time scheduling, demand response and remote programming/diagnostic functions are enabled with installation of the LMBC-300 Network Bridge for system connectivity.
  4. To integrate occupancy detection control with the HVAC System, use a LMRL-100 Isolated Relay Interface.