Conference Room - ASHRAE 90.1 (2016) Compliant

Space <5000Ft2
Dimming with Wireless DLM product

ASHRAE Conference Room

 

 

Bill Of Materials

Quantity

Part Number

Description

5

LMRC-611MCC

Wireless 1-Relay Room Controller, 0-10V Dimming Metering, Contact Closure

2

LMPC-600 Wireless Ceiling Mount Occupancy Sensor, Extended Lens

2

LMSW-605 Wireless Digital 5-Button Scene Switch 

1

LMDL-600 Wireless Photosensor, Open Loop

1

LMPL-611-20M Wireless 1 Relay Plug Load Controller, Metering

Optional

LMPC-600-RPM Recessed Plenum Mounting Kit

Optional

LMDL-600-RPM Recessed Plenum Mounting Kit

Quantity

:

5

Part Number: LMRC-611MCC

Description

:

Wireless 1-Relay Room Controller, 0-10V Dimming Metering, Contact Closure

Quantity

:

2

Part Number: LMPC-600

Description

:
Wireless Ceiling Mount Occupancy Sensor, Extended Lens

Quantity

:

2

Part Number: LMSW-605

Description

:
Wireless Digital 5-Button Scene Switch 

Quantity

:

1

Part Number: LMDL-600

Description

:
Wireless Photosensor, Open Loop

Quantity

:

1

Part Number: LMPL-611-20M

Description

:
Wireless 1 Relay Plug Load Controller, Metering

Quantity

:

Optional

Part Number: LMPC-600-RPM

Description

:
Recessed Plenum Mounting Kit

Quantity

:

Optional

Part Number: LMDL-600-RPM

Description

:
Recessed Plenum Mounting Kit

Code Requirements

Code

Description

9.4.1.1(a)

Local Control Device

9.4.1.1(b, c) Manual On / Partial Auto On
9.4.1.1(d) Bi-level Control
9.4.1.1(e) Auto Daylight Responsive
9.4.1.1(h) Auto Full Off
8.4.2 Auto Receptacle Control

Code

:

9.4.1.1(a)

Description

:

Local Control Device

Code

:
9.4.1.1(b, c)

Description

:
Manual On / Partial Auto On

Code

:
9.4.1.1(d)

Description

:
Bi-level Control

Code

:
9.4.1.1(e)

Description

:
Auto Daylight Responsive

Code

:
9.4.1.1(h)

Description

:
Auto Full Off

Code

:
8.4.2

Description

:
Auto Receptacle Control

Sequence of Operation

  1. General lighting (a, adz1, adz2) auto On to 50% and controlled receptacles auto On when occupancy detected
  2. Manual On/Off/Dim general lighting (a, adz1, adz2) and down lighting (b, c, d) with scene switches.
  3. Scene settings:
    1. General Lighting       (a, adz1, adz2) 100%, (b) 0%, (c) 0%, (d) 0%
    2. Projection                   (a, adz1, adz2) 0%, (b) 75%, (c) 50%, (d) 0%
    3. Conferencing             (a, adz1, adz2) 50%, (b) 50%, (c) 25%, (d) 50%
    4. All Off                          (a, adz1, adz2) 0%, (b) 0%, (c) 0%,
  4. Lighting in primary (adz1) and secondary (adz2) daylight zones will continuously dim based on daylight contribution to maintain at least 35FC at task level.
  5. Auto off all lighting, controlled receptacles, A/V systems within 20 minutes of occupants leaving.

Design Considerations

  1. Time scheduling and remote programming functions are enabled by connectivity to a LMBR-650 Border Router.
  2. To integrate occupancy detection control with the HVAC system, use contact outputs on the LMRC-611MCC.
  3. System Configuration Tools:
    a. Standalone rooms use the configuration application (Apple or Android)
    b. Networked rooms (with the LMBR-650) can be configured using LMCS-100.