NEWS: Legrand acquires Focal Point
A Chicago-based, vertically integrated leader in architectural lighting and acoustic solutions.
Menu
Search
Menu

Multi-Stall Restroom - ASHRAE 90.1 (2016) Compliant

Dimming with Wireless DLM Product

 

Bill Of Materials

Quantity

Part Number

Description

2 LMRC-611MCC

Wireless 1-Relay Room Controller, 0-10V Dimming Metering, Contact Closure

4 LMPC-600 Wireless Ceiling Mount Occupancy Sensor, Extended Lens
2 LMDM-601 Wireless 1-Button Dimming Switch

Optional

LMPC-600-RPM Recessed Plenum Mounting Kit

Quantity

:
2
Part Number: LMRC-611MCC

Description

:

Wireless 1-Relay Room Controller, 0-10V Dimming Metering, Contact Closure

Quantity

:
4
Part Number: LMPC-600

Description

:
Wireless Ceiling Mount Occupancy Sensor, Extended Lens

Quantity

:
2
Part Number: LMDM-601

Description

:
Wireless 1-Button Dimming Switch

Quantity

:

Optional

Part Number: LMPC-600-RPM

Description

:
Recessed Plenum Mounting Kit

Code Requirements

Code

Description

9.4.1.1(a)

Local Control Device

9.4.1.1(h) Auto Full Off
6.4.3.4.4 Ventilation Fan Controls

Code

:

9.4.1.1(a)

Description

:

Local Control Device

Code

:
9.4.1.1(h)

Description

:
Auto Full Off

Code

:
6.4.3.4.4

Description

:
Ventilation Fan Controls

Sequence of Operation

  1. For each restroom independently, lighting auto On to 100% and exhaust fan auto on when occupancy detected.
  2. Manual On/Off with local control switch.
  3. Auto off all lighting and exhaust fans for each restroom independently within 20 minutes of occupants leaving. 

Design Considerations

  1. Time scheduling and remote programming functions are enabled by connectivity to a LMBR-650 Border Router.
  2. To integrate occupancy detection control with the HVAC system, use contact outputs on the LMRC-611MCC.
  3. System Configuration Tools:
    a. Standalone rooms use the configuration application (Apple or Android)
    b. Networked rooms (with the LMBR-650) can be configured using LMCS-100.