Small Conference Room - ASHRAE 90.1 (2016) Compliant

Dimming with Wireless DLM product

ASHRAE Small Conference Room

 

Bill Of Materials

Quantity

Part Number

Description

3 LMRC-611MCC

Wireless 1-Relay Room Controller, 0-10V Dimming Metering, Contact Closure

1

LMPX-600-1 Wireless PIR Corner/Wall Occupancy Sensor, Extended Lens

1

LMSW-605 Wireless Digital 5-Button Scene Switch

1

LMPL-611-20M Wireless 1 Relay Plug Load Controller, Metering

Quantity

:
3
Part Number: LMRC-611MCC

Description

:

Wireless 1-Relay Room Controller, 0-10V Dimming Metering, Contact Closure

Quantity

:

1

Part Number: LMPX-600-1

Description

:
Wireless PIR Corner/Wall Occupancy Sensor, Extended Lens

Quantity

:

1

Part Number: LMSW-605

Description

:
Wireless Digital 5-Button Scene Switch

Quantity

:

1

Part Number: LMPL-611-20M

Description

:
Wireless 1 Relay Plug Load Controller, Metering

Code Requirements

Code

Description

9.4.1.1(a)

Local Control Device

9.4.1.1(b, c) Manual On / Partial Auto On
9.4.1.1(d) Bi-level Control
9.4.1.1(h) Auto Full Off
8.4.2 Auto Receptacle Control

Code

:

9.4.1.1(a)

Description

:

Local Control Device

Code

:
9.4.1.1(b, c)

Description

:
Manual On / Partial Auto On

Code

:
9.4.1.1(d)

Description

:
Bi-level Control

Code

:
9.4.1.1(h)

Description

:
Auto Full Off

Code

:
8.4.2

Description

:
Auto Receptacle Control

Sequence of Operation

  1. General lighting (a) auto On to 50% and controlled receptacles auto On when occupancy detected.
  2. Manual On/Off/Dim of general lighting (a) and down lighting (b, c) with scene switch.
  3. Scene settings
    • General Lighting (a) 100%, (b) 0%, (c) 0%
    • Presentation (a) 75%, (b) 50%, (c) 100%
    • Video (a) 20%, (b) 75%, (c) 0%
    • All Off  (a) 0%, (b) 0%, (c) 0%
  4. Auto off all lighting and controlled receptacles within 20 minutes of occupants leaving.

Design Considerations

  1. Time scheduling and remote programming functions are enabled by connectivity to a LMBR-650 Border Router.
  2. To integrate occupancy detection control with the HVAC system, use contact outputs on the LMRC-611MCC.
  3. System Configuration Tools:
    a. Standalone rooms use the configuration application (Apple or Android)
    b. Networked rooms (with the LMBR-650) can be configured using LMCS-100.