Multi-Stall Restroom - IECC® (2015) Compliant

On/Off Switching with Analog Product

Multi-Stall Restroom Stand-Alone Solution Reflected Ceiling Diagram


Bill Of Materials

Quantity

Part Number

Description

4

BZ-150 Power Pack

2

 

UT-305 Ceiling Mount Ultrasonic Occupancy Sensor

2

LVSW-102 2-Button Wall Switch

Quantity

:

4

Part Number: BZ-150

Description

:
Power Pack

Quantity

:

2

 

Part Number: UT-305

Description

:
Ceiling Mount Ultrasonic Occupancy Sensor

Quantity

:

2

Part Number: LVSW-102

Description

:
2-Button Wall Switch

Code Requirements

Code

Description

C405.2.1

Occupancy Sensor Controls

C405.2.1.1

Manual On / Partial Auto On

C405.2.2.3

Manual Controls

C405.2.2.2

Light Reduction Control

Code

:

C405.2.1

Description

:
Occupancy Sensor Controls

Code

:

C405.2.1.1

Description

:
Manual On / Partial Auto On

Code

:

C405.2.2.3

Description

:
Manual Controls

Code

:

C405.2.2.2

Description

:
Light Reduction Control

Sequence of Operation

  1. For each restroom independently, lighting auto On for 100% illumination when occupancy detected.
  2. Manual On/Off and 50% reduction control of lighting (a, b) with wall switch.
  3. Auto Off all lighting for each restroom independently within 20 minutes of occupants leaving.

Design Considerations

  1. Time scheduling, demand response and remote programming/diagnostic functions are available using Wattstopper Digital Lighting Management networked products.
  2. To integrate occupancy detection control with the HVAC or exhaust system, use a UT-300 occupancy sensor with isolated relay.