text.skipToContent text.skipToNavigation

Single-Gang Deep Switch and Outlet Box, 100-Pack

Switch & Outlet Box is rated 2.0 out of 5 by 1.
  • y_2022, m_12, d_3, h_21
  • bvseo_bulk, prod_bvrr, vn_bulk_3.0.34
  • cp_1, bvpage1
  • co_hasreviews, tv_0, tr_1
  • loc_en_US, sid_S122R, prod, sort_[SortEntry(order=HELPFULNESS, direction=DESCENDING), SortEntry(order=POSITIVE_FEEDBACK, direction=DESCENDING), SortEntry(order=SUBMISSION_TIME, direction=DESCENDING)]
  • clientName_legrand
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getAggregateRating, 31ms
  • REVIEWS, PRODUCT

Single-gang, deep switch and outlet box. Durable, impact-resistant thermoplastic boxes contain innovative extras that cut installation time. Extra deep for dimmers, GFCIs and thermostats, yet suitable for 2x4 construction. Provides two quick click entries. Qty 100.

Color Gray

Features

  • Quick Click feature secures devices quickly and easily
  • Does not strip when over-torqued
  • Durable, impact-resistant thermoplastic box
  • Innovative extras that cut installation time

Specifications

General Info
Product Line Pass & Seymour
Color Gray
UPC Number 785007207194
Country Of Origin United States
Construction Thermoplastic
Standard UL Listed
Dimensions
Cubic Capacity 22 cu in
Additional Information
Product Environmental Profile Yes
Technical Information
Cable Entry No in
Number of Outlets 1

Resources

Reviews

Rated 2 out of 5 by from Poor quality Cover/device screws either slide right in or strip out before ever getting tight
Date published: 2022-10-03
  • y_2022, m_12, d_3, h_21
  • bvseo_bulk, prod_bvrr, vn_bulk_3.0.34
  • cp_1, bvpage1
  • co_hasreviews, tv_0, tr_1
  • loc_en_US, sid_S122R, prod, sort_[SortEntry(order=HELPFULNESS, direction=DESCENDING), SortEntry(order=POSITIVE_FEEDBACK, direction=DESCENDING), SortEntry(order=SUBMISSION_TIME, direction=DESCENDING)]
  • clientName_legrand
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getReviews, 4ms
  • REVIEWS, PRODUCT

Questions & Answers

Can I mount an S122R from the ceiling to hang a LED disc light form it or a smoke detector on it? The disc light weighs less than a smoke detector.

Asked by: Anonymous
The UL number is for this box but the rating is for 6 lbs. if mounted vertically. When dealing with inspectors who have little to no common sense every word matters!!
Answered by: Anonymous
Date published: 2022-06-20

Does the S118W outlet box have a fire rating?

Asked by: Tony S
Yes, it is UL Classified for 2 Hour Fire Resistance.
Answered by: Legrand Technical Support
Date published: 2022-08-11

what type of plastic is used in your boxes

Asked by: jim c
Our boxes are made of a durable, impact resistant Thermoplastic material.
Answered by: Legrand Technical Support
Date published: 2021-10-14

what is the distance between boxes in opposing directions in a 1 hr rated wood stud rated wall

Asked by: mycitylady
Hello Mycitylady, Thank you for your question, Please review the following response below that is referenced from the attached UL 2hour fire rating document. UL 2hour Fire Rating: Part S122R Clearance between boxes and cutouts in ceiling shall not exceed 1/8 in. The area of openings for boxes shall not aggregate more than 31 sq in. Per 100 sq ft of ceiling area with no opening exceeding 8 sq in. No box shall be located within 4.5ft of another box. Best regards, Justin
Answered by: Justin
Date published: 2022-06-29

what is the dimension of this box? how deep is it?

Asked by: sallymarjoriee
The dimension for the S122R box is: Length 3 3/4" Width 2 1/4" Depth 3 3/8"
Answered by: Legrand Technical Support
Date published: 2021-04-21

Can the 18r single gang be mounted in clinging and how much weight can it hold 

Asked by: Derek
The S118R is designed for wall vertical mount and if a box is not marked with a specific weight then it has a 6lbs maximum fixture rating.
Answered by: Legrand Technical Support
Date published: 2021-01-07

can these be installed in a 2 hour firewall within 2' of an oppsing outlet

Asked by: Jack70
For use in fire resistance floor-ceiling assemblies constructed with wood joists, wood flooring and gypsum wallboard ceilings with 2 hr or less classification periods. Clearance between boxes and cutouts in ceiling shall not exceed 1/8 in. The area of openings for boxes shall not aggregate more than 31 sq in. per 100 sq ft of ceiling area with no opening exceeding 8 sq in. No box shall be located within 4.5 ft of another box.
Answered by: Legrand Technical Support
Date published: 2020-11-21

Does the Legrand Slater electrical bracket box meet residential building code if fiberglass insulation is used in the walls where the box is located?

Asked by: RJen
UL Classified - All Slater Plastic Boxes are Underwriters Laboratories Listed. Slater Plastic Boxes shown that are UL Classified for Fire Resistance meet the requirements of UL263 and have a two hour fire resistance rating. These boxes may be used in fire resistant walls and ceilings. Installation information for Slater Plastic Boxes Classified for Fire Resistance may be found in the UL Fire Resistance Directory under category CEYY for Legrand(see attached).
Answered by: Legrand Technical Support
Date published: 2022-03-09
  • y_2022, m_12, d_1, h_21CST
  • bvseo_bulk, prod_bvqa, vn_bulk_3.0.34
  • cp_1, bvpage1
  • co_hasquestionsanswers, tq_11
  • loc_en_US, sid_S122R, prod, sort_[SortEntry(order=LAST_APPROVED_ANSWER_SUBMISSION_TIME, direction=DESCENDING)]
  • clientName_legrand
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getContent, 44ms
  • QUESTIONS, PRODUCT