LMCP 0-10V PANEL w/8-RELAY MAX CAPACITY
LMCP8-10V
Wattstopper
Bazaarvoice SAP Hybris Integration Version 2.8.1
The LMCP series panels are available for Dimming (LMCPx-10V) or Switched(LMCPx) control of lighting and plug loads. The panels can be networked together to enable
automation through out an entire facility. The HDR panel relays respond to inputs from Digital Lighting Management (DLM) switches, occupancy sensors, daylight sensors, input modules and 0-10V outputs on dimming panel
models.
- Send
- Save as PDF
-
Added to Favorites Go to favoritesRemove from favorites?Something went wrong. Please try again later.
Features
- Dimming panels dim 0-10V lighting loads as well as switch lighting and plug loads
- Switching panels switch lighting and plug loads
- Native BACnet communications for network control solutions
- Easy setup via LMCT-100 handheld configuration tool
- HDR relays include a switch for manual override even when panel is powered off
- Compatible with Digital Lighting Management switches, sensors and input devices
- 99 control groups accessible via handheld configuration tool
Specifications
General Info
Product Line | Wattstopper | ||
Color | Nickel | ||
UPC Number | 754182947485 | ||
Country Of Origin | United States |
Additional Information
Product Has Potential to Contribute to LEED | Yes | This product contributes to earning credits in the LEED rating system. Visit our LEED with Legrand webpage for more information. |
Resources
Installation Instructions
Reviews
Bazaarvoice SAP Hybris Integration Version 2.8.1
Questions & Answers
Does this panel have battery backup capabilities that prevent the loss of program and time settings for not fewer than 10 hours, if power is interrupted?
yes, the schedule clock is battery backed for at least 21 days
Date published: 2023-10-15
Does the 0-10v relay panel have an internal timeclock to meet the energy code?
Wattstopper LMCP panels with 0-10 volts has an internal time clock that needs to be set once it's installed. This will allow you to set up your programming that's needed and also meet your energy code.
Date published: 2023-01-25
Is the LMCP panel available for exterior applications?
Wattstopper does not offer a NEMA rated enclosure for outdoor use. Please contact Wattstopper Technical Support for more information at 800-879-8585.
Date published: 2022-04-13
Do the Relays in the panel have a torque value that needs to be met when terminating?
The torque rating is specified on the label of the HRD relay that provides the SCCR rating of the relay. The torque applied to the screw terminal cannot exceed 16 inch-pounds.
Date published: 2022-11-22
Bazaarvoice SAP Hybris Integration Version 2.8.1