Dual Tech Wall Switch Occupancy Sensor, 347V, Ivory
DSW-301-347-I
Wattstopper
Bazaarvoice SAP Hybris Integration Version 2.8.1
The DSW-301 dual technology wall switch sensor turns lights OFF and ON based on occupancy. It combines the benefits of passive infrared (PIR) and ultrasonic detection technologies. The DSW-301 replaces existing wall switches and fits behind a standard decorator wall plate.
Voltage
347 VAC
- 120/277 VAC
- 347 VAC
- Send
- Save as PDF
-
Added to Favorites Go to favoritesRemove from favorites?Something went wrong. Please try again later.
Features
- Zero-crossing for long relay life
- Vandal resistant lens combines precise coverage with durability
- Selectable walk-through mode turns lights off three minutes after initial occupancy if no motion is detected after the first 30 seconds
- Test mode allows quick and easy adjustments
- Selectable audible alert for impending shutoff
- In automatic mode, sensor returns automatically to Auto-ON after lights are turned off manually; ideal for presentations
- Four occupancy logic options to customize control to meet application needs
Specifications
General Info
Product Line | Wattstopper | ||
Color | Ivory | ||
UPC Number | 754182935659 | ||
Country Of Origin | China |
Dimensions
Product Width US | 3.8 in | ||
Product Weight US | 2.3 lb | ||
Product Volume US | 37.1 cu in | ||
Product Depth US | 3.8 in | ||
Product Height US | 6.5 in |
Technical Information
Sensor Type | Occupancy | ||
Amperage | 4.3 A | ||
Wattage | 1500 W | ||
Voltage | 347 V, 347 V |
Reviews
Bazaarvoice SAP Hybris Integration Version 2.8.1
Questions & Answers
DSW-301, instructions don’t show a wiring diagram with a three way switch, will it not work that way or do have to have 2 -301 devices?
Hello,
The DSW-301 supports multi-way wiring, which requires multiple DSW-301 ( up to 4 sensors) to complete a 3-way configuration.
Best Regards,
Justin
Date published: 2023-10-11
can you install a dsw-301 occ switch along with a DT-305 ceiling occ sensor? with a bz-50 PP?
It is recommended that you chose one or the other. The sensors will not work in conjunction with each other.
Date published: 2023-09-12
I have 3 x 301's in a row. please post a wiring diagram for more than 2 devices in a row. Also when should use the walk thru mode ?
We do not have a diagram that shows more than 2 sensors. You should connect the primary switch, install the second per the diagram and then mirror the same with the remaining 2 switches. A short hallway that is not used often or a storage closet application are places where Walk through mode may be appropriate.
Date published: 2023-09-12
Can this be use on one side of a 3 way system with the other switch a regular 3 way>
Hello Cody,
The DSW301 Occupancy sensor supports Multi-way functionality for use with additional DSW301 sensors. The DSW301 will not work with a traditional 3-way switch and must be paired with another DSW301 for 3-way applications.
Best Regards,
Technical Support
Date published: 2023-06-16
Can I control bathroom exhaust fan with this switch?
Hello,
Occupancy Dual Technology Sensors DSW301 will support the following loads:
120VAC; 50/60Hz or 277VAC; 50/60Hz
120VAC: 0-1000W ballast, LED, tungsten, 1/6 hp
277VAC: 0-1200W ballast, LED, 1/6 hp
Best Regards,
Technical Support
Date published: 2023-05-26
Will a DSW301W work without a ground connection?
Hello,
DSW301W - The ground wire (green) must be fastened to ground for the sensor to work properly.
Best Regards,
Technical Support
Date published: 2023-05-04
Is the watt stopper dsw 301w also a 3-way switch
Hello,
DSW-301-W supports the following Multi-way features: (Total of 4 Sensors)
The Multi-Way capability is available on all models. Sensors can easily be wired together for convenient control of a common load. When wiring this way, only use 300 series sensors. Multi-Way in 300 series is not compatible with prior sensor models.
The following principles apply for Multi-Way:
• All units should be on the same phase.
• All units can see each other’s push-button events and respond accordingly.
• All units can see each other’s PIR trigger event. The response will be determined by the Light Level setting and/or conditions of the space of the detecting sensor.
• The time delay for all units is defined by the unit with the smallest time delay
Best Regards,
Technical Support
Date published: 2023-03-06
Is there any way to purchase a replacement plastic lens for this? During construction, mine popped off and was swept up and disappeared, and it seems like such a cheap little piece that should be replaceable as it is easy to remove and/or damage.
The lens is not available as an individual part. Please contact Wattstopper Technical Support for further information. 800-879-8585.