NEWS: Legrand acquires Focal Point
A Chicago-based, vertically integrated leader in architectural lighting and acoustic solutions.
Menu
Search
Menu

Breakroom|Kitchen - ASHRAE 90.1 (2016) Compliant

Dimming with Wireless DLM Product

ASHRAE Breakroom

 

Bill Of Materials

Quantity

Part Number

Description

2

LMRC-611MCC Wireless 1-Relay Room Controller, 0-10V Dimming Metering, Contact Closure 

1

LMPC-600 Wireless PIR Corner/Wall Occupancy Sensor, Extended Lens

2

LMDM-601 Wireless 1-Button Dimming Switch
1 LMPL-611-20M Wireless 1 Relay Plug Load Controller, Metering

Optional

LMDL-600-RPM Recessed Plenum Mounting Kit

Quantity

:

2

Part Number: LMRC-611MCC

Description

:
Wireless 1-Relay Room Controller, 0-10V Dimming Metering, Contact Closure 

Quantity

:

1

Part Number: LMPC-600

Description

:
Wireless PIR Corner/Wall Occupancy Sensor, Extended Lens

Quantity

:

2

Part Number: LMDM-601

Description

:
Wireless 1-Button Dimming Switch

Quantity

:
1
Part Number: LMPL-611-20M

Description

:
Wireless 1 Relay Plug Load Controller, Metering

Quantity

:

Optional

Part Number: LMDL-600-RPM

Description

:
Recessed Plenum Mounting Kit

Code Requirements

Code

Description

9.4.1.1(a)

Local Control Device

9.4.1.1(b, c)

Manual On / Partial Auto On

9.4.1.1(d)

Bi-level Control

9.4.1.1(h)

Auto Full Off

9.4.1.3

Special Application Lighting

8.4.2

Auto Receptacle Control

Code

:

9.4.1.1(a)

Description

:

Local Control Device

Code

:

9.4.1.1(b, c)

Description

:

Manual On / Partial Auto On

Code

:

9.4.1.1(d)

Description

:

Bi-level Control

Code

:

9.4.1.1(h)

Description

:

Auto Full Off

Code

:

9.4.1.3

Description

:

Special Application Lighting

Code

:

8.4.2

Description

:

Auto Receptacle Control

Sequence of Operation

  1. Lighting (a) auto On to 50% and controlled receptacles auto On when occupancy detected.
  2. Manual On/Off and bi-level 50% control of general lighting (a, b) with wall switch occupancy sensor.
  3. Manual On/Off control under cabinet lighting (c) with switch.
  4. Auto off all lighting and controlled receptacles within 20 minutes of occupants leaving.

Design Considerations

  1. Time scheduling and remote programming functions are enabled by connectivity to a LMBR-650 Border Router.
  2. To integrate occupancy detection control with the HVAC system, use contact outputs on the LMRC-611MCC.
  3. System Configuration Tools:
    a. Standalone rooms use the configuration application (Apple or Android)
    b. Networked rooms (with the LMBR-650) can be configured using LMCS-100.