Small Private Office - ASHRAE 90.1 (2013) Compliant

≤250 SqFt

Dimming with DLM product

ASHRAE Small Private Office

 

Bill Of Materials

Quantity

Part Number

Description

1

LMRC-102 2-Relay Room Controller

1

LMDW-102 2-Button Dual Tech Wall Switch Occupancy Sensor

1

WRC-TX-LM Plug Load RF Transmitter

4

WRC-20-1 Plug Load Half Controlled Receptacle

-

LMRJ Pre-Terminated Cable

Quantity

:

1

Part Number: LMRC-102

Description

:
2-Relay Room Controller

Quantity

:

1

Part Number: LMDW-102

Description

:
2-Button Dual Tech Wall Switch Occupancy Sensor

Quantity

:

1

Part Number: WRC-TX-LM

Description

:
Plug Load RF Transmitter

Quantity

:

4

Part Number: WRC-20-1

Description

:
Plug Load Half Controlled Receptacle

Quantity

:

-

Part Number: LMRJ

Description

:
Pre-Terminated Cable

Code Requirements

Code

Description

9.4.1.1(a)

Local Control Device

9.4.1.1(b, c) Manual On / Partial Auto On
9.4.1.1(d) Bi-level Control
9.4.1.1(h) Auto Full Off
8.4.2 Auto Receptacle Control

Code

:

9.4.1.1(a)

Description

:

Local Control Device

Code

:
9.4.1.1(b, c)

Description

:
Manual On / Partial Auto On

Code

:
9.4.1.1(d)

Description

:
Bi-level Control

Code

:
9.4.1.1(h)

Description

:
Auto Full Off

Code

:
8.4.2

Description

:
Auto Receptacle Control

Sequence of Operation

  1. Lighting (a) auto On to 50% and controlled receptacles auto On when occupancy detected.
  2. Manual On/Off and bi-level 50% control of general lighting (a, b) with wall switch occupancy sensor.
  3. Auto off all lighting and controlled receptacles within 20 minutes of occupants leaving.

Design Considerations

  1. Receptacle control can be designed using either an RF transmitter with receptacle RF receivers, or can be hardwired to receptacles using an LMPL-101 Plug Load Room Controller.
  2. Time scheduling, demand response and remote programming/diagnostic functions are enabled with installation of the LMBC-300 Network Bridge for system connectivity.
  3. To integrate occupancy detection control with the HVAC System, use a LMRL-100 Isolated Relay Interface.