NEWS: Legrand acquires Universal Electric Corporation
Global leader in the development of flexible, customizable power distribution systems and manufacturer of STARLINE and U-S Safety Trolley suites of products.
Menu
Search
Menu

Large Private Office - CA Title 24 (2016) Compliant

Space >100Ft2, Bldg >10,000Ft2
Dimming with DLM product

 

TITLE24 Large Private Office

Bill Of Materials

Quantity

Part Number

Description

1 LMRC-111 1-Relay Room Controller, 0-10V Dimming
1 LMDX-100 Corner Mount Dual Tech Occupancy Sensor
1 LMDM-101 1-Button Dimming Wall Switch
1 LMLS-400 Photosensor, Closed Loop

1

LMPL-101 Plug Load Room Controller

1

LMBC-300 Wired Network Bridge

-

LMRJ Pre-Terminated Cable

Quantity

:
1
Part Number: LMRC-111

Description

:
1-Relay Room Controller, 0-10V Dimming

Quantity

:
1
Part Number: LMDX-100

Description

:
Corner Mount Dual Tech Occupancy Sensor

Quantity

:
1
Part Number: LMDM-101

Description

:
1-Button Dimming Wall Switch

Quantity

:
1
Part Number: LMLS-400

Description

:
Photosensor, Closed Loop

Quantity

:

1

Part Number: LMPL-101

Description

:
Plug Load Room Controller

Quantity

:

1

Part Number: LMBC-300

Description

:
Wired Network Bridge

Quantity

:

-

Part Number: LMRJ

Description

:
Pre-Terminated Cable

Code Requirements

Code

Description

130.1(a)1-3 Area Controls
130.1(b) Multi-Level Controls
130.1(c)5 Occupancy Sensor Shut-Off Controls
130.1(d)1.B Auto Daylighting Control
130.1(e) Demand Responsive Controls
130.5(d) Receptacle Control

Code

:
130.1(a)1-3

Description

:
Area Controls

Code

:
130.1(b)

Description

:
Multi-Level Controls

Code

:
130.1(c)5

Description

:
Occupancy Sensor Shut-Off Controls

Code

:
130.1(d)1.B

Description

:
Auto Daylighting Control

Code

:
130.1(e)

Description

:
Demand Responsive Controls

Code

:
130.5(d)

Description

:
Receptacle Control

Sequence of Operation

  1. Lighting auto On to 50% and controlled receptacles auto On when occupancy detected.
  2. Manual On/Off/Dim lighting with dimmer switch.
  3. Lighting in primary daylight zone will continuously dim based on daylight contribution to maintain at least 35FC at task level.
  4. Auto off all lighting and controlled receptacles within 20 minutes of occupants leaving.
  5. A network demand response signal will reduce lighting level by a minimum of 15% of total lighting power.

    Design Considerations

    1. Receptacle control can be designed using either an RF transmitter with receptacle RF receivers, or can be hardwired to receptacles using an LMPL-101 Plug Load Room Controller.
    2. Demand Response, time scheduling and remote programming functions are enabled by the LMBC-300 Network Bridge connectivity. If Demand Responsive 15% lighting power reduction (Title 24 130.1(e)) for this space is offset by more aggressive light reduction in other spaces, connection to the lighting control network may not be necessary, thereby not requiring the LMBC-300 Network Bridge and associated network wiring.
    3. To integrate occupancy detection control with the HVAC System, use a LMRL-100 Isolated Relay Interface.