Private Restroom - CA Title 24 (2016) Compliant

Space <100Ft2, Bldg >10,000Ft2
On/Off Switching with line voltage wallbox product

TITLE24 Private Restroom

Bill Of Materials

Quantity

Part Number

Description

1 PW-301 Wallbox PIR Occupancy Sensor

Quantity

:
1
Part Number: PW-301

Description

:
Wallbox PIR Occupancy Sensor

Code Requirements

Code

Description

130.1(a)1-3 Area Controls
130.1(c)5 Occupancy Sensor Shut-Off Controls
130.1(e) Demand Responsive Controls
120.2(e)1 Mechanical Controls

Code

:
130.1(a)1-3

Description

:
Area Controls

Code

:
130.1(c)5

Description

:
Occupancy Sensor Shut-Off Controls

Code

:
130.1(e)

Description

:
Demand Responsive Controls

Code

:
120.2(e)1

Description

:
Mechanical Controls

Sequence of Operation

  1. Lighting and fan are manually controlled On/Off with occupancy sensor switch.
  2. Lighting and fan will auto Off within 20 minutes of occupants leaving. 

Design Considerations

  1. Demand Response, time scheduling and remote programming functions are enabled by the LMBC-300 Network Bridge connectivity. If Demand Responsive 15% lighting power reduction (Title 24 130.1(e)) for this space is offset by more aggressive light reduction in other spaces, connection to the lighting control network may not be necessary, thereby not requiring the LMBC-300 Network Bridge and associated network wiring.