Small Private Office - IECC® (2018) Compliant

On/Off Switching with DLM Product

Small Private Office Reflected Ceiling Diagram - IECC (2018) DLM Solution

Bill Of Materials

Quantity

Part Number

Description

1

LMRC-102 2-Relay Room Controller

1

LMDW-102 2-Button Dual Tech Wall Switch Occupancy Sensor

-

LMRJ Pre-Terminated Cable

Quantity

:

1

Part Number: LMRC-102

Description

:
2-Relay Room Controller

Quantity

:

1

Part Number: LMDW-102

Description

:
2-Button Dual Tech Wall Switch Occupancy Sensor

Quantity

:

-

Part Number: LMRJ

Description

:
Pre-Terminated Cable

Code Requirements

Code

Description

C405.2.1 Occupancy Sensor Controls
C405.2.1.1 Manual On / Partial Auto On
C405.2.2.2 Light Reduction Controls
C405.2.5 Manual Controls

Code

:
C405.2.1

Description

:
Occupancy Sensor Controls

Code

:
C405.2.1.1

Description

:
Manual On / Partial Auto On

Code

:
C405.2.2.2

Description

:
Light Reduction Controls

Code

:
C405.2.5

Description

:
Manual Controls

Sequence of Operation

  1. Lighting (a) auto On to 50% when occupancy detected.
  2. Manual On/Off and 50% reduction control of lighting (a,b) with wall switch occupancy sensor.
  3. Auto Off all lighting within 20 minutes of occupants leaving. 

    Design Considerations

    1. Although not required by IECC, receptacle control can be added to this space for additional energy savings using either an RF transmitter with receptacle RF receivers, or hardwired receptacles using an LMPL-101 Plug Load Room Controller.
    2. Time scheduling, demand response and remote programming/diagnostic functions are enabled with installation of the LMBC-300 Network Bridge for system connectivity.
    3. To integrate occupancy detection control with the HVAC System, use a LMRL-100 Isolated Relay Interface.