The LDCM-PL-120-277-010V takes a 0-10V dimming signal and a fixed line voltage input and converts it to a reverse phase dimmed output for up to 1000W for a 277V load and 450W for a 120V load. One LDCM-PL can be used per run up to the maximum wattage. The LDCM-PL can be used per run up to the maximum wattage. The LDCM-PL is rated to directly mount to a junction box in a plenum space for easier installations and to meet building requirements.
- Send
- Save as PDF
-
Added to Favorites Go to favoritesRemove from favorites?Something went wrong. Please try again later.
Specifications
General Info
| Color | Gray | ||
| Product Series | LDCM | ||
| Type | Converter | ||
| Material | Polycarbonate | ||
| Finish | Matte | ||
| Application Sector | Commercial | ||
| Product Line | Wattstopper | ||
| Country Of Origin | China | ||
| Installation Location | Ceiling | ||
| Warranty Type | 5-Year | ||
| Standard | UL 8750, CSA C22 No. 250.13, ETL, cETL, RoHS | ||
| UPC Number | 754182948840 |
Dimensions
| Product Depth US | 1.96 in | ||
| Product Height US | 3.39 in | ||
| Product Volume US | 46.5 cu in | ||
| Product Width US | 7.0 in | ||
| Product Weight US | 0.91 lb |
Technical Information
| Current Draw | 3.8 A | ||
| Dimming Compatibility | 0-10 V, Reverse Phase | ||
| Has Battery | No | ||
| Indoor/Outdoor | Indoor | ||
| Input Voltage | 120/277 VAC | ||
| Line Frequency | 60 Hz | ||
| Location Rating | Damp | ||
| Mounting Type | 1/2 in Knockout | ||
| Number of Relays | 0 | ||
| Operating Temperature | -20°-40°C, -4°-104°F | ||
| Operating Temperature Max | 104 °F | ||
| Operating Temperature Min | -4 °F | ||
| Operating Humidity | 5-95% RH (Non-Condensing) | ||
| Maximum Power | 1000 W @ 277 VAC, 450 W @ 110-120 VAC | ||
| Storage Temperature | 23° - 176° F |
Resources
Cutsheet
Installation Instructions
Customer CAD PDF
Reviews
Bazaarvoice SAP Hybris Integration Version 2.8.1
Questions & Answers
I have a Vantage DIN rail mounted Low-Voltage Output Station (LVOS) is used for the control LED, CFL, and CCFL lighting loads that requiring either 0-10 or PWM for dimming control. Could control the LDCM-PL with my Vantage module ?
Yes, your Vantage LVOS-0-10-PWM module can control the LDCM-PL (Linear Dimming Control Module - Plenum Rated).
Since the LDCM-PL requires a 0-10V dimming signal and the LVOS-0-10-PWM provides exactly that, you can use the LVOS to control the LDCM-PL. Just ensure:
You connect the 0-10V output from the LVOS to the dimming input of the LDCM-PL.
The line voltage is supplied separately to the LDCM-PL as it handles the ELV output.
Date published: 2025-09-09
Can this be used to convert dimmed line voltage (output of a dimming motion sensor) to a 0-10vdc output signal to control flood lights?
The LDCM-PL-120-277-010V is not designed to convert dimmed line voltage into a 0–10VDC control signal. Instead, it works the opposite way—it takes a 0–10V dimming signal and uses it to control a reverse-phase dimmed line voltage output.
It’s commonly used to control reverse-phase dimmable fixtures (such as LED or electronic low-voltage lighting) using 0–10V devices like LMRC room controllers.
If you need to convert dimmed line voltage to a 0–10V signal, this device would not be suitable. You would likely need a different solution designed specifically for that type of signal conversion.
Date published: 2025-05-13
On the load side of this device do you need a separate neutral for lights or does the dimming just dim on the load hot?
Thank you for your question. A separate output neutral is necessary and cannot be shared.
Date published: 2024-09-04
Does this device require a switched hot? Will the ELV output turn off or go to a low end 1% / 5% / 10% when 0-10V dimming voltage falls to 1V or below?
The LDCM-PL requires 110-120 or 277 constant voltage. The performance will depend on the fixture. The LDCM provides dimming only, it does not switch. We would use it in conjunction with a room controller which would switch the load to off when the load is 0% in the DLM system.
Date published: 2024-07-11
Bazaarvoice SAP Hybris Integration Version 2.8.1
Recently Viewed
Added to Favorites
Go to favorites
Remove from favorites?
Something went wrong. Please try again later.
TP28W | Pass and Seymour
Combination Openings, 2 Toggle Switch and 1 Duplex Receptacle, 3-Gang
Added to Favorites
Go to favorites
Remove from favorites?
Something went wrong. Please try again later.
R26USBACWCCV6 | radiant Collection
Charge any device with USB Type-A and USB Type-C connections built into a tamper-resistant outlet.
$45.84
Added to Favorites
Go to favorites
Remove from favorites?
Something went wrong. Please try again later.
5362I | Pass and Seymour
Hard Use Spec Grade Receptacle, Back and Side Wire, 20A, 125V
Added to Favorites
Go to favorites
Remove from favorites?
Something went wrong. Please try again later.
SS1426 | Pass and Seymour
Combination Openings, 1 Blank and 1 Decorator, 2-Gang, 302/304 Stainless Steel
Added to Favorites
Go to favorites
Remove from favorites?
Something went wrong. Please try again later.
G4000B-10 | Wiremold
The work horse of surface raceway systems.
Added to Favorites
Go to favorites
Remove from favorites?
Something went wrong. Please try again later.
HT1015WH10PK | On-Q
The Flexible Mini Pass-Through Grommet is an in-wall cable management solution meant for speed!
$32.46
Added to Favorites
Go to favorites
Remove from favorites?
Something went wrong. Please try again later.
3864 | Pass and Seymour
Power Outlets